SF₆ moisture calculator

Convert an SF₆ dew point reading to ppmV and mg/kg, see the dew point inside the compartment at its filling pressure, and check the result against IEC limits and the lowest enclosure temperature.

LiveYORK · SF₆ moisture
Measured value
ppmV (µL/L)
mg/kg (ppmW)

Most portable SF₆ hygrometers measure at atmospheric pressure

°C

Used to check for condensation on insulators

ppmV
Water content
—ppmV
Dew point at filling pressure
—°C
Dew point at 1 atm
—°C
Dew point vs pressure for this gas
mg/kg (ppmW)
—
ppmV (µL/L)
—
Water vapour pressure at filling
—
Ratio to IEC 60480 limit
—

YORK instrument for SF₆ moisture
    Send these parameters to an engineer →Opens the enquiry form with your inputs filled in.

    Why moisture in SF₆ matters

    Water in SF₆ can condense on insulator surfaces when the equipment cools, and reacts with arc decomposition products to form corrosive acids. Because the gas is held at several bar, the dew point inside the compartment is much higher than the dew point a portable hygrometer reads at atmospheric pressure. The condensation check therefore uses the dew point at filling pressure.

    Reference limits used by the tool

    DocumentScopeWater limit
    IEC 60376New technical-grade SF₆≤ 25 mg/kg
    IEC 60480:2019SF₆ for re-use< 200 µL/L (ppmV)
    Equipment manufacturerIn-service limitsAs stated in the manual, often as dew point at rated pressure or ppmV at 20 °C

    Conversions

    • ppmV (µL/L) to mg/kg: multiply by 18.015 / 146.06 = 0.1233.
    • Dew point at another pressure: the water mole fraction stays the same, the water vapour partial pressure scales with total pressure.
    • Water vapour pressure from Sonntag (1990), over ice below 0 °C unless you choose dew point over water.

    Measuring SF₆ moisture on site

    The YORK DM9600P portable chilled mirror hygrometer measures the dew point directly, down to −60 °C frost point, which covers the IEC 60376 and IEC 60480 limits with margin. SF₆ is a potent greenhouse gas: use fittings designed for SF₆ and recover the sample gas rather than venting it.

    Frequently asked questions

    How do I convert SF6 dew point to ppmV?

    Calculate the water vapour pressure at the dew point and divide it by the total pressure at which the dew point was measured. For example, −36 °C frost point at atmospheric pressure is about 200 ppmV, or about 25 mg/kg.

    What is the moisture limit for SF6 re-use under IEC 60480?

    IEC 60480:2019 sets a water limit below 200 µL/L (ppmV) for SF₆ that is to be re-used in electrical equipment. New technical-grade SF₆ under IEC 60376 is limited to 25 mg/kg.

    Why is the dew point at filling pressure higher than the measured one?

    A portable hygrometer usually measures the gas after it has expanded to atmospheric pressure. Inside the compartment the same gas is at several bar, so its water vapour partial pressure, and therefore its dew point, is higher. That is the value that matters for condensation.

    Checking SF₆ quality in GIS or breakers?

    Ask us about the DM9600P portable chilled mirror for SF₆ checks. Tell us the equipment type, filling pressure and the limits you work to.

    YORK InstrumentYORK Instrument Middle East · Dubai · WhatsApp +971 55 137 4866 · yorkinstrument.ae
    Calculation for engineering estimation only; see method and limits above. v2026.11