  2. Guides
  3. SF₆-free switchgear moisture

Industry guide · power grids

SF₆-free switchgear: measuring moisture in alternative insulating gases

Saudi Electricity Company plans SF₆-free switchgear, and new EU equipment is moving off SF₆ from 2026. The replacement gases still have to be dry: here are typical limits and how to check them.

Why SF₆-free switchgear is coming

Utilities are moving away from SF₆, the most potent greenhouse gas used in industry. In February 2025 the Saudi Electricity Company signed a memorandum of understanding with Hitachi Energy to adopt SF₆-free technology for high- and medium-voltage switches and circuit breakers. In Europe, Regulation (EU) 2024/573 bans putting into operation new switchgear that relies on F-gases in steps from 2026.

EU switchgear categoryBan on new equipment from
Medium voltage up to 24 kV1 January 2026
Medium voltage above 24 kV up to 52 kV1 January 2030
High voltage above 52 kV up to 145 kV (and up to 50 kA), gases with GWP ≥ 11 January 2028
High voltage above 145 kV or above 50 kA, gases with GWP ≥ 11 January 2032

EU dates for orientation; Gulf utilities set their own technical specifications. Exceptions apply under the regulation.

Alternative gases still need dry gas

The replacements are gas mixtures, mostly based on CO₂: fluoronitrile (C4-FN) mixtures with CO₂ and oxygen, fluoroketone (C5-FK) mixtures, and technical air (nitrogen and oxygen) combined with vacuum interrupters. Moisture still has to be kept low: water lowers the dielectric strength, can condense on insulators and reacts with decomposition products. So the dew point is checked at filling, at commissioning and during maintenance, just as with SF₆.

C4-FN mixture (manufacturer handbook)Moisture limit
After filling, gas compartment with adsorber≤ −10 °C frost point at filling pressure
After filling, compartment without adsorber≤ −15 °C frost point at filling pressure
During service life≤ −5 °C frost point at filling pressure
Technical-grade C4-FN (draft IEC 63360)≤ 70 ppmv H₂O

Limits are referred to IEC 62271-1. The equipment manufacturer's values always govern.

How to measure

  • Chilled mirror for mixtures. A chilled mirror hygrometer measures the dew point directly, so it suits CO₂-based mixtures and technical air as well as SF₆. For field work use the portable DM9600P or DM9600PL (to −70 °C frost point); in the laboratory the DM9700.
  • Pressure basis. Limits are given as frost point at filling pressure. Measure at near-atmospheric pressure and convert to the filling pressure of the compartment.
  • Do not vent the gas. Fluorinated mixtures still have a global warming potential: return the sample to a recovery cylinder rather than releasing it.
  • Same routine, different gas. Keep the fittings clean and dry and allow the reading to settle; a wet hose is the most common cause of a high result.

Frequently asked questions

Do SF₆-free switchgear gases need moisture checks?

Yes. Water lowers dielectric strength and can condense on insulators, so the dew point is checked at filling, commissioning and maintenance, as with SF₆.

What is the moisture limit for C4-FN mixtures?

One manufacturer handbook gives ≤ −10 °C frost point at filling pressure after filling (compartments with adsorber), ≤ −15 °C without adsorber, and ≤ −5 °C in service, referred to IEC 62271-1. The equipment maker's values govern.

Can a chilled mirror hygrometer measure CO₂-based switchgear mixtures?

Yes. It measures the dew point directly, so it is suitable for C4-FN/CO₂ mixtures and technical air as well as SF₆.

Is Saudi Arabia adopting SF₆-free switchgear?

The Saudi Electricity Company signed a memorandum of understanding with Hitachi Energy in February 2025 to adopt SF₆-free technology for high- and medium-voltage switches and circuit breakers.