Power generation and grid: where to measure moisture, O₂ and SF₆

Follow fuel gas into the turbine, hydrogen around the generator and power out through the SF₆ switchgear. Each numbered point shows what is measured, the typical limit and the instrument that fits.

H₂ SUPPLYCO₂ PURGEFUEL GASTO GRIDPOWERH₂-COOLED GENERATORH₂ DRYERH₂-COOLEDGENERATORFUEL GAS SKIDGAS TURBINEHRSG /BOILERSTACKSTEP-UPTRANSFORMERSF₆ SWITCHGEAR (GIS)SF₆ GAS CART1H₂O2H₂O3H₂ %4H₂O5SF₆6H₂O7O₂8H₂O
YORK instrumentIntegrated system (supplied through YORK)

Tap a numbered point. Swipe the diagram sideways on a phone.

Request a quote for this point →
Auto tour
Project list 0 →

⤓ Download the 2-page PDF application note

How the process works

A gas-fired plant uses three gases that need watching: fuel gas going into the turbine, hydrogen cooling the generator, and SF₆ insulating the switchgear. Moisture is the main enemy in all three, so most of these points are dew point measurements, many of them made with portable instruments during maintenance.

  1. Fuel gas conditioning. The fuel gas skid filters and heats the gas so that it reaches the turbine superheated above its water and hydrocarbon dew points.
  2. Gas turbine and heat recovery. Exhaust from the turbine raises steam in a heat recovery boiler (HRSG). Flue gas oxygen shows how much excess air is used.
  3. Hydrogen-cooled generator. Large generators are cooled with hydrogen because it cuts windage loss. A dryer keeps the hydrogen dry, and CO₂ is used to purge the casing before filling or opening it.
  4. Step-up and switchyard. The transformer raises the voltage, and gas-insulated switchgear filled with SF₆ connects the plant to the grid.
  5. SF₆ handling. Gas carts recover, filter and refill SF₆ during maintenance. Recovered gas is checked before it goes back into service.

Measurement points at a glance

#PointMeasuresTypical value / limitRecommended solution
1Generator casing gas (dryer inlet)Water dew point of the hydrogenNo single OEM limit is published; one utility targets ≤ −18 °C (0 °F), preferably −29 °C (−20 °F). Field readings of −7 to +21 °C have been reportedDPT990-EX, DPT-600 Plus-EX
2Hydrogen dryer outletWater dew pointShould read well below the casing gas: the difference shows the dryer is workingDPT990-EX
3Generator casing gasH₂ purity; H₂ in CO₂ and CO₂ in air during purgingOne plant runs above 90 % and vents and refills below 90 %; each 1 % drop in purity adds about 1 % windage lossIntegrated system: thermal-conductivity H₂ purity analyzer with three ranges (H₂ in air, H₂ in CO₂, CO₂ in air)
4SF₆ switchgear compartmentMoisture in SF₆ (ppmv / dew point)Equipment dew points typically −60 to −5 °C. IEC 62271-1 reference ≈ 574 ppmv at 700 kPa; manufacturer limits 70–1000 ppmv by equipment typeDM9600P, DM9600PL, DPT-600 Plus
5SF₆ compartment after faultsSF₆ purity and decomposition products (SO₂, SOF₂, HF)Air + CF₄ ≤ 2 % for re-use; decomposition products tolerable to 100 ppmv, 50 ppmv for re-use (CIGRE)Integrated system: SF₆ purity analyzer (speed of sound, thermal conductivity or NDIR) and decomposition-product analyzer
6Recovered SF₆ for re-useMoisture in SF₆CIGRE re-use limits: 120 ppmv at 2 MPa, 320 ppmv at 500 kPa, 1600 ppmv at 100 kPaDM9600P, DPT-600 Plus
7HRSG / boiler flue gasExcess oxygenAbout 2–3 % O₂ for natural gas; each 15 % cut in excess air raises efficiency about 1 % (US DOE)POA3500; Integrated system: in-situ zirconia O₂ probe for combustion control
8Gas turbine fuel gas skidWater dew pointFuel must be supplied at least 11 °C (20 °F) above its highest dew point (one turbine OEM specification)DPT810, DPT990-EX

Values are typical figures from published specifications and technical literature. Your contract, licensor or plant specification always governs.

Getting reliable readings

  • Know the pressure. SF₆ moisture limits depend on the filling pressure of each compartment, so convert between dew point and ppmv at the right pressure.
  • Same season, same temperature. SF₆ readings change with temperature: correct them to 20 °C and compare readings taken in the same season.
  • Return the gas. Use a measuring setup that returns the SF₆ sample instead of venting it.
  • Hydrogen is a hazardous area. Online dew point on the generator uses an explosion-proof transmitter; for portable checks in the hydrogen area use the explosion-proof DPT-600 Plus-EX.
  • Wet and dry O₂. In-situ zirconia probes read on a wet basis and extractive analyzers on a dry basis. Compare like with like.

Frequently asked questions

Why measure dew point in a hydrogen-cooled generator?

Moisture from seal oil, cooler leaks or air ingress corrodes the generator and promotes retaining-ring cracking. Purity analyzers do not measure water, so a dew point instrument is needed on the casing gas and the dryer outlet.

What moisture limit applies to SF₆ switchgear?

It depends on the equipment and its filling pressure. IEC 62271-1 gives a reference of about 574 ppmv at 700 kPa, and manufacturers set limits between 70 and 1000 ppmv by equipment type.

Can recovered SF₆ be reused?

Yes, if it meets the re-use limits. CIGRE gives moisture limits of 120 ppmv at 2 MPa, 320 ppmv at 500 kPa and 1600 ppmv at 100 kPa, plus limits for air, CF₄ and decomposition products.

Does YORK supply hydrogen purity and zirconia O₂ analyzers?

Yes, as an integrated system through YORK's partner integration factory, together with the YORK dew point and oxygen instruments.

Maintaining generators or SF₆ switchgear?

Tell us the equipment, gas and pressures, and we will recommend portable or online instruments.