Free tool · Power and GIS
SF₆ moisture calculator
Convert an SF₆ dew point reading to ppmV and mg/kg, see the dew point inside the compartment at its filling pressure, and check the result against IEC limits and the lowest enclosure temperature.
↧ Download offline version (single HTML file, works without internet)
- mg/kg (ppmW)
- —
- ppmV (µL/L)
- —
- Water vapour pressure at filling
- —
- Ratio to IEC 60480 limit
- —
Why moisture in SF₆ matters
Water in SF₆ can condense on insulator surfaces when the equipment cools, and reacts with arc decomposition products to form corrosive acids. Because the gas is held at several bar, the dew point inside the compartment is much higher than the dew point a portable hygrometer reads at atmospheric pressure. The condensation check therefore uses the dew point at filling pressure.
Reference limits used by the tool
| Document | Scope | Water limit |
|---|---|---|
| IEC 60376 | New technical-grade SF₆ | ≤ 25 mg/kg |
| IEC 60480:2019 | SF₆ for re-use | < 200 µL/L (ppmV) |
| Equipment manufacturer | In-service limits | As stated in the manual, often as dew point at rated pressure or ppmV at 20 °C |
Conversions
- ppmV (µL/L) to mg/kg: multiply by 18.015 / 146.06 = 0.1233.
- Dew point at another pressure: the water mole fraction stays the same, the water vapour partial pressure scales with total pressure.
- Water vapour pressure from Sonntag (1990), over ice below 0 °C unless you choose dew point over water.
Measuring SF₆ moisture on site
Buying in Saudi Arabia? See SF₆ moisture analyzers in Saudi Arabia.
The YORK DM9600P portable chilled mirror hygrometer measures the dew point directly, down to −60 °C frost point, which covers the IEC 60376 and IEC 60480 limits with margin. SF₆ is a potent greenhouse gas: use fittings designed for SF₆ and recover the sample gas rather than venting it.
Frequently asked questions
How do I convert SF6 dew point to ppmV?
Calculate the water vapour pressure at the dew point and divide it by the total pressure at which the dew point was measured. For example, −36 °C frost point at atmospheric pressure is about 200 ppmV, or about 25 mg/kg.
What is the moisture limit for SF6 re-use under IEC 60480?
IEC 60480:2019 sets a water limit below 200 µL/L (ppmV) for SF₆ that is to be re-used in electrical equipment. New technical-grade SF₆ under IEC 60376 is limited to 25 mg/kg.
Why is the dew point at filling pressure higher than the measured one?
A portable hygrometer usually measures the gas after it has expanded to atmospheric pressure. Inside the compartment the same gas is at several bar, so its water vapour partial pressure, and therefore its dew point, is higher. That is the value that matters for condensation.
More engineering tools
- Dew point calculatorConvert pressure dew point to atmospheric dew point, ppmV, mg/m³ and lb/MMscf, with a pipe condensation check.
- ISO 8573-1 air class checkerFind the ISO 8573-1 water class of your compressed air from a dew point reading at any pressure.
- Analyzer selectorAnswer five questions and get the YORK moisture, oxygen or CO₂ analyzer that fits your application.
- Nitrogen purge calculatorHow long, and how much nitrogen, to purge a vessel or pipeline down to a target O₂ level.
- Natural gas water content calculatorConvert water dew point at line pressure to lb/MMscf, mg/Sm³ and ppmV, and check against a pipeline specification.
- Hydrogen purity checker (ISO 14687)Check water, oxygen and other impurities against ISO 14687 Grade D for fuel-cell hydrogen.
- Sample line response timeTransport time and T95 response for a gas sample line, from tubing size, length, flow and pressure.
- Moisture and oxygen unit converterppmV, ppmW, mg/m³, mg/Sm³, lb/MMscf and dew point for moisture; %, ppm, ppb and partial pressure for oxygen.
Checking SF₆ quality in GIS or breakers?
Ask us about the DM9600P portable chilled mirror for SF₆ checks. Tell us the equipment type, filling pressure and the limits you work to.