H₂O · Chilled mirror
YORK DM9600P portable chilled mirror hygrometer
The DM9600P is a battery-powered chilled mirror hygrometer for site work, from −60 °C frost point to +20 °C dew point. Because a chilled mirror measures dew point directly, engineers use it to check moisture in SF₆ and SF₆-free switchgear and as a portable reference when verifying fixed dew point transmitters on instrument air and nitrogen.

| Model | DM9600P |
|---|---|
| Type | Portable chilled mirror hygrometer |
| Range | −60 °C frost point to +20 °C dew point |
| Principle | Chilled mirror, air cooled |
| Built in | Pressure sensor, electronic flow meter |
| Data and power | Data logging to SD card; rechargeable lithium battery |
| Use | Non-flammable gases in safe areas; sample pressure up to 4 barg |
| Lead time | 6 to 8 weeks |
| Warranty | 12 months from shipment |
| Regional contact | Dubai, UAE — covers the GCC |
Product catalog (PDF) · certificate copies are sent with quotations.
Where it is used
| Job | What you check |
|---|---|
| SF₆ and SF₆-free switchgear | Moisture in the insulating gas against the equipment limit; see the SF₆ moisture calculator and SF₆-free switchgear guide |
| Verifying fixed transmitters | Side-by-side check of instrument air or nitrogen dew point transmitters at site |
| Industrial gas deliveries | Moisture in nitrogen, argon and oxygen at the point of use |
| Climatic and test chambers | Dew point in the chamber during qualification |
Good practice on site
- Reduce the sample to 4 barg or less; the built-in pressure sensor lets you report dew point at the measured pressure and convert with the dew point calculator.
- Use short stainless steel lines and let the mirror reach a stable dew or frost layer before recording.
- Below 0 °C a chilled mirror can briefly hold supercooled dew; wait for a stable frost point reading.
- Keep the mirror clean; contamination slows the response and shifts the reading.
- YORK chilled mirror hygrometers are low-pressure instruments for non-flammable gases in safe areas; they are not explosion-proof and are not intended for natural gas, hydrogen or other flammable gases.
DM9600P or another YORK instrument?
| If you need… | Choose |
|---|---|
| Continuous rack-mount monitoring to −70 °C frost point | DM9700 |
| Rack-mount to −80 °C frost point, VCR fittings | DM9800 |
| Laboratory reference to −90 °C frost point | DM9900 |
| Field checks of flammable gases or in hazardous areas | A metal-oxide instrument: DPT-600 Plus-EX or DPT990-EX |
Ordering in the UAE and GCC
Send your enquiry to our Dubai team with:
- the gas and the equipment (for example GIS compartments);
- the expected dew point and pressure;
- whether you need SD logging reports;
- quantity.
We reply with a quotation for the DM9600P. Instruments are shipped from the factory with export documents, 6 to 8 weeks from order confirmation. The SF₆ switch rooms of substations are usually not hazardous areas, so the DM9600P can be used there. For Saudi substations, see SF₆ moisture analyzers in Saudi Arabia.
See all dew point meters and analyzers available in the UAE.
Questions about the DM9600P
What is the range of the DM9600P?
−60 °C frost point to +20 °C dew point.
Can the DM9600P measure moisture in SF₆?
Yes. It measures dew point directly; convert to ppmv with the SF₆ moisture calculator and compare with the equipment limit.
What is the difference between the DM9600P and the DM9600PL?
The DM9600PL reaches −70 °C frost point; the DM9600P reaches −60 °C frost point.
Can it be used for natural gas or other flammable gases?
No. YORK chilled mirror hygrometers are low-pressure instruments (up to 4 barg) and are not explosion-proof; they are for non-flammable gases in safe areas. For natural gas, see the DPT990-EX.
How do I get a quotation in the UAE?
Email dubai@yorkinstrument.com or WhatsApp +971 55 137 4866 with the gas, dew point range and quantity.