Sulfur recovery, fuel gas and flare: where to measure

Most analyzers in a sulfur recovery unit are specialised sulfur and combustion analyzers that YORK supplies as integrated systems. YORK instruments cover the flare header oxygen, the purge nitrogen and the instrument air.

ACID GASSOUR GASAIRLIQUID SULFURTO VALVESREFINERY FUEL GASTO HEATERSRELIEF & BLOWDOWN HEADERPURGE GAS (N₂ / FUEL GAS)CLAUS FURNACEWASTE HEATBOILERCONVERTERSHYDRO-GENATIONQUENCHTGUABSORBERINCINERATORSTACKINSTRUMENTAIR DRYERFUEL GAS KO DRUMFLARE KO DRUMFLARE1H₂S:SO₂2H₂3O₂4O₂5H₂S6O₂7GC8O₂9H₂O
YORK instrumentIntegrated system (supplied through YORK)

Tap a numbered point. Swipe the diagram sideways on a phone.

Request a quote for this point →
Auto tour
Project list 0 →

⤓ Download the 2-page PDF application note

How the process works

The sulfur recovery unit turns H₂S from the amine regenerator and sour water stripper into liquid sulfur, and the tail gas unit cleans up what is left. Here the key analyses are sulfur ratios and combustion control, which need specialised analyzers. YORK supplies them as integrated systems, alongside its own instruments for oxygen and dew point.

  1. Claus furnace. Part of the H₂S burns with air to SO₂; the air rate is trimmed from the tail gas H₂S:SO₂ ratio.
  2. Waste heat boiler and converters. The gas is cooled and passes catalytic converters, where H₂S and SO₂ react to sulfur that condenses as a liquid.
  3. Tail gas unit. A reducing-gas burner and hydrogenation reactor turn the remaining sulfur compounds into H₂S, which a quench column and amine absorber remove.
  4. Incinerator. Residual H₂S is burned before the gas leaves the stack.
  5. Fuel gas and flare. The fuel gas header feeds the heaters; the flare header collects relief and blowdown gas and is kept free of air by purge gas.

Measurement points at a glance

#PointMeasuresTypical value / limitRecommended solution
1Claus tail gasH₂S to SO₂ ratio2:1 is the stoichiometric reference; operators often target 2:1 to 4:1Integrated system: UV air-demand analyzer
2Tail gas unit, after hydrogenationExcess hydrogenAbout 2.1 % at 10 % excess air (simulated example)Integrated system: thermal-conductivity H₂ analyzer
3Tail gas unit, reducing-gas burnerOxygen ingressFiring above about 90 % of stoichiometric air risks oxygen reaching the hydrogenation catalystIntegrated system: zirconia O₂ analyzer
4Incinerator stackExcess oxygenPlant-specific: set to keep destruction efficiency and permit compliancePOA3500; Integrated system: in-situ zirconia O₂ analyzer
5Refinery fuel gas headerH₂SSet by the emission permit for the heaters (limit not reproduced here)Integrated system: H₂S analyzer
6Flare headerOxygen (air ingress)No single published limit; an O₂ signal can trigger purge or make-up gas injectionIntegrated system: O₂ analyzer qualified for wet sour gas in Zone 1/2
7Flare vent gasHeating value and compositionSet by local flare regulations (limit not reproduced here)Integrated system: process GC or calorimeter
8Purge and blanket nitrogenOxygen (%)Keep oxygen below the limiting oxygen concentration with margin (NFPA 69), e.g. about ≤ 10 % for methanePGA500-EX
9Instrument air headerPressure dew pointAt least 10 °C below the lowest ambient temperature, and never above 4 °C at line pressure (ISA-7.0.01)DPT810, DM9200, DPT-600 Plus-EX

Values are typical figures from published specifications and technical literature. Your contract, licensor or plant specification always governs.

Getting reliable readings

  • Heat the sulfur lines. Sulfur vapour condenses in cold sample lines and plugs them.
  • Wet and dry basis. In-situ zirconia reads oxygen on a wet basis; an extractive analyzer after a cooler reads dry. Compare like with like.
  • Hazardous areas. Flare and fuel gas points are in classified areas: use explosion-proof analyzers or a certified analyzer shelter.
  • Purge before work. Confirm the oxygen level with a portable analyzer before opening equipment or starting hot work.

Frequently asked questions

Why is the H₂S:SO₂ ratio measured in the Claus tail gas?

The ratio controls the combustion air to the Claus furnace. About 2:1 gives the best conversion; excess air sends SO₂ to the tail gas unit.

Why monitor oxygen in a flare header?

Air drawn into the header or stack can create an explosive mixture. An oxygen analyzer warns the operator and can trigger purge or make-up gas.

Which sulfur recovery points does YORK cover?

YORK instruments cover flare header oxygen, purge nitrogen and instrument air dew point. Sulfur ratio, hydrogen, zirconia oxygen and GC points are supplied by YORK as integrated systems.