العربية
  1. Home
  2. Applications
  3. Medical gases in hospitals

Application

Hospitals: medical air dew point and oxygen checks

Checking the water content of medical air and the oxygen content of medical air and concentrator oxygen at the hospital gas plant, with YORK dew point meters and oxygen analyzers.

Why it matters

Hospitals make medical air on site with compressors, dryers and filters, and receive oxygen as liquid or produce it with PSA oxygen concentrators. Water in medical air can condense in the pipeline and terminal units and supports corrosion and microbial growth, so the dryer outlet is checked for dew point. The oxygen content of medical air, and the purity of oxygen from a concentrator, are checked before the gas goes to the wards.

Typical requirements

Hospital standards such as HTM 02-01 and ISO 7396-1 cover the design and testing of medical gas pipeline systems and refer to the pharmacopoeia for gas quality. The values usually required are:

GasQuality itemTypical requirement
Medical airWater≤ 67 ppm, about −46 °C dew point at atmospheric pressure
Medical airOxygen19.5 to 23.5 %
Medical airCarbon dioxide≤ 500 ppm
Medical oxygen (liquid supply)Oxygen assay≥ 99.0 %
Oxygen from a PSA concentrator ("oxygen 93 %")Oxygen assayTypically about 93 %; the accepted range is set by the monograph and the hospital specification

These are typical figures. The hospital specification, the national standard and the applicable pharmacopoeia always govern. The 67 ppm limit is about −46 °C at atmospheric pressure; at line pressure the dew point is higher, so convert with the dew point calculator before comparing a reading with the limit.

Where to measure

#PointWhat is checkedYORK instrument
1Medical air plant, after the dryers and filtersDew point (water content)DPT830 in-line; DPT-600 Plus for spot checks
2Medical air plant outletOxygen content (19.5 to 23.5 %)PGA530 in-line; POA300 portable
3Medical air plant outletCarbon dioxidePGA520
4Oxygen concentrator outletOxygen purityPGA530 in-line; POA300 portable
5Pipeline and terminal units, after work on the systemDew point and oxygen spot checksDPT-600 Plus, POA300

CO, SO₂, NO + NO₂ and oil in medical air need other analyzer types, which YORK can supply as part of an integrated system. See all points in the medical gas measurement map.

Taking reliable readings

  • Measure after the dryers and filters, where the air leaves the plant, and record the pressure at the sample point.
  • YORK dew point instruments accept up to 4 barg. Reduce the pressure, measure, and report the dew point at the stated pressure.
  • Use short stainless steel sample lines; plastic tubing gives off moisture and makes the reading wetter than the gas.
  • Check the oxygen analyzer in air (20.9 % O₂) before the job and purge the sample line.
  • CO₂ or CO at the plant outlet usually points to a poorly placed air intake.

YORK analyzers are industrial instruments for checking gas quality at the plant and in the pipeline. They are not medical devices and are not used on patients. Certificates are provided per model with quotation.

Questions we are asked

What dew point is required for medical air?

The water limit usually applied is 67 ppm or less, about −46 °C dew point at atmospheric pressure, from the pharmacopoeia monographs that hospital standards such as HTM 02-01 and ISO 7396-1 refer to. The hospital specification governs.

How do you check the purity of a hospital oxygen concentrator?

Connect an oxygen analyzer to the concentrator outlet: a PGA530 in-line for continuous monitoring or a POA300 portable for spot checks, both 0 to 100 % O₂. Concentrators typically deliver about 93 % oxygen; the accepted range is set by the monograph and the hospital specification.

Which YORK instruments are used in a hospital gas plant?

A DPT830 in-line or DPT-600 Plus portable dew point meter for medical air water content, a PGA530 or POA300 oxygen analyzer for medical air and concentrator oxygen, and a PGA520 for CO₂.

Are YORK analyzers certified as medical devices?

No. They are industrial gas analyzers for plant and pipeline quality checks, not medical devices. Certificates are provided per model with quotation.

Suggested YORK instruments

All medical gas points with limits: medical gases: where to measure moisture, O₂ and CO₂. Converting units? Use the moisture and oxygen unit converter.

Equipping a hospital gas plant?

Tell us the gases, the plant capacity, the pressure at the sample points and the checks you need, and we will propose the instruments.